Skip to content

UART Interface

The UART management interface allows communication with and configuration of the W-BACnet module. The interface is comprised of two digital signals (VDD max):

  • TX - Transmitter Signal
  • RX - Receiver Signal

Connect the UART cable's RX to the UART_MGMT_TX and TX to UART_MGMT_RX pin. Pin assignments can be found here.

Interface Description

Configuration

The UART management interface has the following communication parameters:

Baudrate Parity Stop bits
115200 None 1

Timing requirements

Each UART frame is separated by 100 ms of silence on the bus. Sending frames with less than 100 ms in between the first frame's end and the second frame's start will result in unexpected results.

UART commands

UART commands and responses are comprised of ASCII characters. The user should enter each command separately by considering the timing requirements. Commands are split into two categories: Read and Write commands.

The usage example further down shows how the APP_MODE register is read.

Syntax

UART commands start with either the character r or w, which respectively denote the read or write command operation. The first character is followed by the separator :, and a register name (see the list of registers). In the case of write commands, the separator can be used again at this point to specify additional write parameters. Finally, the command is terminated with a carriage return followed by a new line: "\r\n".

Additionally, the syntax has the following properties:

  • Numeric values are always interpreted and written in decimal form.
  • All text is case insensitive, meaning commands can also start with R or W. This also means that any register name can be written as ex. REG_NAME, or reg_name, or even rEg_NaMe. For the sake of consistency, we specify the command operation in lower case and the register name in upper case.

Reads

Read commands have the following format, where REG_NAME is a placeholder for any readable register (see the list of registers):

r:REG_NAME\r\n

When a read command is successful, the response follows the format below, where REG_NAME is a placeholder for any readable register, and VALUE is a placeholder for the value read from the register:

ok:REG_NAME:VALUE\r\n

Some registers have more than one value, each one separated (like RS485_CONFIG):

ok:REG_NAME:VALUE1:VALUE2:VALUE3\r\n

It is also possible for a register to have no values, as can be the case with SERVER_ADDRESSES when no BACnet devices are detected:

ok:REG_NAME:\r\n

A real example of multiple values when reading (and writing) can be seen in the section about the RS485_CONFIG register.

Writes

Write commands have the following format, where REG_NAME is a placeholder for any writable register (see the list of registers), and PARAM can be any valid write parameter:

w:REG_NAME:PARAM\r\n

Some registers take more than one parameter:

w:REG_NAME:PARAM1:PARAM2\r\n

In the case of a successful write command, the response should reflect exactly the content of the original request, but instead leading with an ok instead of a w. See the examples further down for examples.

Responses and errors

Responses follow almost the same format as reads and writes, but instead begin with either ok: when the command was successful, otherwise error:. Error messages are generated when the message parser deems the command invalid. For example, if the message doesn't terminate with \r\n, the message error:INVALID_TERMINATION is generated.

Syntax Examples

/* Read examples */

/* The response 4 shows that the module is in commissioning mesh mode */
>> r:APP_MODE\r\n
>> ok:APP_MODE:4\r\n

/* The fields after the register name represents baudrate = 9600,
   Parity = Even(E) and stop bit = 1 */
>> r:RS485_CONFIG\r\n
>> ok:RS485_CONFIG:9600:E:1\r\n

/* There is no Register with name 'APP' */
>> r:APP\r\n
>> error:UNKNOWN_REGISTER\r\n

/* The command should be terminated with both carriage return '\r'
   and new line '\n' */
>> r:APP_MODE\n
>> error:INCORRECT_TERMINATION\r\n


/* Write examples */

/* The response shows that register is written successfully with value 2 */
>> w:APP_MODE:2\r\n
>> ok:APP_MODE:2\r\n

/* The response shows that register is written with baudrate = 38400,
   Parity = None(N) and stop bit = 2 */
>> w:RS485_CONFIG:38400:N:2\r\n
>> ok:RS485_CONFIG:38400:N:2\r\n

/* There is no register named 'APP' */
>> w:APP\r\n
>> error:UNKNOWN_REGISTER\r\n

Registers

The table below lists all registers available in the UART management interface. The first column denotes the name of the register. The "Type" column denotes whether the register is read-only (R), write-only (W), or read-write (R/W).

The final column, "Reset value", denotes the default value of the register. That is, when the module is factory new, or immediately after DEVICE_RESET has been set to 1, the registers values will be set to their reset values. A reset value of - means either the register is write-only, or that it can be different and/or change depending on circumstance. For instance, the reset value of ANTENNA_SELECTOR depends on if the module is an MWA-N2 or MWA-N3 module since only the MWA-N3 has an internal antenna (see Integration page for information about MWA's).

Multi-valued registers like RS485_CONFIG show separated reset values, in the order that they are read & written.

Register name Type Reset value
NETWORK_STATUS R -:-
APP_MODE R/W 4
BOOTLOADER_ENABLED W -
FIRMWARE_VERSION R -:-:-
RS485_CONFIG R/W 0:N:1
DEVICE_RESET W -
NETWORK_RESET W -
SERVER_ADDRESSES R -
ANTENNA_SELECTOR R/W -
BLUETOOTH_ENABLED R/W 0

NETWORK_STATUS

This register is read-only and contains information about the network status of the device. The register holds two values, of which the first indicates whether the device has received network commissioning data; and the second indicates roughly how stable the connection to the network is. To perform consistently successful network operations (e.g., modifying network baudrate or app mode), it is recommended to do them when the value of NETWORK_STATUS is 1:1 or 1:2.

NOTE: Devices in gateway modes will ALWAYS have the value 1 in the LINK_QUALITY field, due to link quality being measured in relation to the gateway itself.

The subsections below show the two values in the order that they will appear, and the meaning of their possible values.

/* The response when reading `NETWORK_STATUS` will look like this: */
>> ok:NETWORK_STATUS:<COMMISSIONING>:<LINK_QUALITY>\r\n

/* Below is an example with real values: */
>> r:NETWORK_STATUS\r\n
>> ok:NETWORK_STATUS:1:1\r\n
COMMISSIONING

Indicates whether any network credentials have been received (i.e. if the device has joined a network).

Value Meaning
0 No commissioning data yet received
1 Valid commissioning data has been received

Indicates the stability of any current network connection.

Value Meaning
0 Not connected to a network
1 Connected, good link
2 Connected, ok link
3 Connected, unreliable link

APP_MODE

This field is read-write, and determines which application mode the device is in. The module, when factory new, boots into mode 0 (None). This is detected by the application, leading to a switch to the default mode 4 (Commissioning Mesh Mode), causing a restart. In other words, the module will restart once after booting in a factory new state. Writing the value 1 to DEVICE RESET will manually factory reset the device. In other words, writing a 0 or 4 to APP_MODE will put the device in Commissioning Mesh Mode.

The Idle mode will prevent the module from performing any networking, therefore putting it in a sort of sleep. No configuration will be erased when switching to this mode, meaning the module can be put back into secure mode and connect to a previously saved network.

Read more about app modes in the Functional Description which describes the commissioning/decommissioning process.

The table below has a list of all possible modes, along with how many restarts are followed by the switching to a particular mode:

Value Meaning Restarts (when written)
0 None (will revert to default) 2
1 Secure Gateway Mode 1
2 Commissioning Gateway Mode 1
3 Secure Mesh Mode 1
4 Commissioning Mesh Mode (default) 1
5 Idle Mode 1

FIRMWARE_VERSION

This register is read-only and contains information about the current version the device is running. The module responds with the firmware version in the following format:

>> r:FIRMWARE_VERSION\r\n
>> ok:FIRMWARE_VERSION:3:2:7\r\n

BOOTLOADER_ENABLED

This register is write-only and can be used to put the device into bootloader/DFU mode, so that the firmware can be updated.

Value Meaning Restarts (when written)
1 Enter bootloader/DFU mode 1

RS485_CONFIG

This register is read-write, and is used to read and configure the following RS485 communication parameters:

  1. Baudrate
  2. Parity
  3. Stop bits

The values are listed in the order in which they are read and written. The example below demonstrates this:

/* Read example */
>> r:RS485_CONFIG\r\n
>> ok:RS485_CONFIG:9600:E:1\r\n

/* Write example */
>> w:RS485_CONFIG:9600:N:1\r\n
>> ok:RS485_CONFIG:9600:N:1\r\n
Baudrate

Standard values (in bits/second) 9600 bps, 19200 bps, 38400 bps, 76800 bps have been tested and verified. Larger values, such as 115200 bps, are allowed but have not been tested by LumenRadio.

PARITY
Value Meaning
N No parity
E Even parity
STOP BITS
Value Meaning
1 One stop bit
2 Two stop bits

DEVICE_RESET

This register is write-only and facilitates factory resets of the module. Factory resetting the module means restoring the device to the state it was in when first booting it. Among other things, this action wipes network credentials, RS485 configurations, and resets all register values.

Performing a device reset leads to 2 restarts of the device, the first one after wiping the configuration, which also sets APP_MODE to 0. After restarting the first time, the application will detect that APP_MODE is 0, leading to a switch to the default app mode, 4. This switch leads to the additional restart, after which the device will be in mesh commissioning mode. Read more about this behavior in the APP_MODE section.

Value Meaning Restarts (when written)
1 Perform a factory reset 2

NETWORK_RESET

This register is write-only, and when set to 1, wipes any saved network credentials. Configurations other than the network, like the RS485 bus parameters, will remain unaffected.

In practice, this means that devices in Secure Mesh Mode or Commissioning Mesh Mode will leave any joined network. For nodes in any of the gateway app modes, a network reset will clear previously saved network credentials. This can happen if the device was previously in a mesh mode and connected to a network, but was later switched to a gateway.

Value Meaning Restarts
1 Wipe network credentials 1 if in Secure Mesh Mode, 0 otherwise

SERVER_ADDRESSES

This register is read-only, and contains the address of each detected BACnet device as a list of separated decimal numbers. If there are no detected devices, reading the register will yield no values, like in the example below:

>> r:SERVER_ADDRESSES\r\n
>> ok:SERVER_ADDRESSES:\r\n

This other example shows how it can look with one device detected:

>> r:SERVER_ADDRESSES\r\n
>> ok:SERVER_ADDRESSES:128\r\n

Finally, having multiple detected devices (as possible with pro versions of the module), looks like this:

>> r:SERVER_ADDRESSES\r\n
>> ok:SERVER_ADDRESSES:32:125:126:127:128\r\n

ANTENNA_SELECTOR

This register is read-write, and facilitates the selection of either the internal antenna or the external antenna for wireless communication. An antenna switch will always cause one restart.

NOTE: MWA-N2 modules do not have internal antennas, meaning they should not change this field under any circumstances (see Integration page for information about MWA's).

Value Meaning Restarts (when changed)
1 Internal antenna selected 1
2 External antenna selected 1

BLUETOOTH_ENABLED

This register is read-write, and allows Bluetooth Low Energy (BLE) advertising for connections to our app. The device will advertise for 1 minute once the Bluetooth is enabled, and then stop. The W-BACnet app can be downloaded from App store and Play store.

When connecting with our app to a device in secure gateway mode with a firmware version of 3.1.0 or above, the app allows for updating of the firmware, and for an overview of the "network map". It is also possible to see which the currently installed firmware version is.

The network map shows how many devices are present in the network, and how their packets are router through the mesh network. The network map also shows which BACnet addresses have been detected to which W-BACnet device. Through the network map, it is also possible to name W-BACnet devices.

It is possible to connect the app to a non-gateway node, but functionality is limited to only viewing the firmware version and the number of BACnet devices connected.

Value Meaning
0 BLE advertising disabled
1 BLE advertising enabled

Usage example

A simple way to get started is with a USB RS232 interface cable, like the one from FTDI found here. Wire such a cable to the W-BACnet module (see pin assignments) and plug the cable into a computer. Launch a serial terminal with the correct parameters, and start communicating with the module.

See below for a simple pseudo-code example that reads the app mode. The UART interface is assumed to be initialized and configured correctly prior to running the example.

/* Buffer must be large enough to accomodate responses */
uint8_t rx_buffer[BUF_SZ];
uint8_t tx_command[BUF_SZ];

/* Prepare the buffer with command to read the app mode */
memcpy(tx_command, "r:APP_MODE\r\n", BUF_SZ);

/* Send command bytes over UART */
uart_tx(tx_command, BUF_SZ);

/* Receive the response over UART */
uart_rx(rx_command, BUF_SZ);

/* The response from module should be "ok:APP_MODE:4\r\n" in commissioning mesh mode */

/* Check the first and last two bytes to confirm that a complete response is received */
if(rx_command[0] == "o" && rx_command [1] == "k" && rx_command [-1] == "\n" && rx_command [-2] == "\r")
{
    int app_mode = rx_command[-3]; // Extract the APP_MODE value
}
Back to top